• Move DIP switch 2 to the ON position to use factory default communication parameters: ---------------------------------------------------------------------- IP Address: 192.168.0.251 Subnet Mask: 255.255.0.0 Default Gateway: 192.168.0.1 DNS: 192.168.0.1 Host port: IP Server, no encryption, port 3001 Communications address:0 * NIC on computer must set to connect to the default settings ---------------------------------------------------------------------- • Open Command Window • Type ping 192.168.0.251 -t (this will put a constant ping on the controller) • Power on the controller • Check ping to see when controller comes online • Once online, move DIP switch 2 to the OFF position and DIP switch 1 to the ON position, this will enable the default user info • Open Internet Explorer • Enter 192.168.0.251 in the address bar • Hit Enter • The Mercury Security login screen will appear, click "Click Here to Login" • Enter the default user info: User Name: admin, password: password • Click Login • Once EP1501 Configuration Manager loads click the Users tab in the left tree • Click the New User button in the Users section • Move all DIP Switches to the OFF position • Enter User Name, Password, and Password again • Click Save • User will now appear in the Users list • Click the Network tab in the left tree • Enter IP address, Subnet Mask, Default Gateway, and DNS info • Click Accept (this will not push setting to board) • Click the Apply Settings tab • Click the Apply Settings, Reboot button (this will push the settings to the board) • In Command Prompt window type: ping NEW IP OF BOARD -t (this will put a constant ping on the controller) • Once board registers setup is complete |
↧